|
|
Direct
Line: 0207 828 0828
Fax: 0207 931 0893 |
Memoranda
submitted to the Environment Sub-Committee of the Environment, Transport
and Regional Affairs Select Committee by the Fire Safety Development
Group:
Inquiry into the potential risk of fire spread in buildings via external
cladding systems
|
|
|
1.
Introduction |
|
1.1 On the 11 June 1999 a wheelchair-bound man died in a tower block
fire in Irvine. We believe that the fire started in a room on the
5th floor and burst out through the window. Within about ten minutes
the fire had spread up seven floors but was contained within the
area of the cladding. The fire broke through into the building,
possibly by means of the area beneath the windows or the windows
themselves, and engulfed the upper nine floors.
1.2 There may have been special circumstances relating to this fire
but nevertheless we consider it highlighted a number of aspects
of fire safety which need to be addressed. These are:
1.3 Firstly, a distinction between products that conform to the
Class 0 standard inherently, or through modification by additives.
1.4 Secondly we seek urgent action from the DETR to regulate the
use of plastics and to reduce the threat to life from toxic smoke
and burning droplets. We have assumed the Committee will be professionally
advised, and have therefore written our evidence accordingly.
1.5 We have been informed that the windows at the corners of the
tower block had been letting in cold and or moisture. In order to
eliminate these problems and also to improve visual appearance,
new window frames of unplastised polyvinyl chloride (uPVC) were
fixed. The exterior wall around the window was covered with glass
reinforced polyester plastic sheet. This gave a picture frame effect
around the window. The glass reinforced polyester sheet was also
extended below the window. We do not know if the fire was spread
by means of the surface of the plastic sheet or whether the fire
spread within a cavity that may have existed between the cladding
and the original external wall.

|
Memoranda
2. Whether a risk is posed by such cladding |
2.1 Regulations in Scotland, England and Wales specify that exterior
cladding should be Class 0 fire performance. Class 0 is the highest
category for surface spread of flame of a material and is defined
in the Approved Document B Fire Safety to the Building Regulations
(England and Wales 1991). This definition is also used in the British
Standard (Scotland) Regulations.
2.2 We believe that there is confusion about the Class 0 standard
for two reasons. Class 0 materials refers to the performance of the
surface of the material, but applies to the total product i.e. the
facing plus any coating, adhesive, paint etc. plus the substrate to
which the facing is bonded. Clearly these other elements will affect
the performance of the cladding in a fire, and will vary with the
nature of the coating, the thickness of the adhesive, the type of
substrate etc.
2.3 A material of limited combustibility can achieve a Class 0 rating
as defined by the regulations but a Class 0 material is not equivalent
to a material of limited combustibility. A material of limited combustibility
is generally a material which is totally non-combustible or which
contains a small amount of combustible material. Combustible materials,
like plastic, wood etc are not materials of limited combustibility
but can achieve Class 0 performance by adding fire retardant chemicals
or facing the combustible material with a metal foil or sheet. Thus
there is a fundamental difference between products that are inherently
Class 0 and products modified to enhance their performance. This serves
to undermine the integrity of the regulations and therefore reduces
fire safety.
2.4 Confusion often occurs because some manufacturers refer to Class
0 products without due consideration for the way the product will
be used or treated. The performance of an external cladding sheet
which, when tested alone and meets the requirements of Class 0, could
easily be downgraded to an inferior level by painting the sheet with
the wrong type of paint.

2.5
We believe that both methods can suffer from technical problems, particularly
for products used for exterior applications, when the additive may
not be durable. With time, the performance will fall to a lower level.
If a facing foil or laminate has been used on the plastic material,
this could be damaged with time or delaminate due to loss of adhesion
between the foil and the substrate. These types of products still
remain combustible and will contribute to fire load in the event of
fire. Higher levels of smoke will be developed when combustible materials
burn than for materials of limited combustibility. Furthermore, in
the case of thermoplastics, they could drip in the event of a fire
and this will exacerbate fire spread.
2.6 It is well known that fire and smoke can spread unhindered in
cavities and for this reason, regulations specify cavities should
be divided at certain intervals depending on the nature of the cavity.
If the requirements had been followed, we do not think the fire would
have spread as described in the newspaper reports but further investigation
should show if cavity barriers were lacking.
2.7 The cladding appears to have helped spread the flame over the
surface and may also have been consumed by the fire. However, it may
not have been considered necessary by the designers/specifiers to
use a product with Class 0 performance as the sheet may have been
classed as a window frame rather than an external cladding. If the
plastic cladding used on the building had a lower spread of flame
than required by regulations or insufficient cavity barriers were
used, then we consider that this system presented a fire risk.
2.8 We understand that the uPVC window frames made a big contribution
to the rapid spread of the fire and its entry into the upper parts
of the building. This would help to explain how the fire could burst
out of the flat where it started, and then manage to get back into
the tower block to destroy the floors above the fifth floor.
2.9 We are concerned about the increasing use of plastic and combustible
materials on the face of buildings and consider that their use should
be examined in more detail. Building regulations do not pay sufficient
consideration to the effect of fires spreading by external means.
Smoke and flames issuing from windows can be very severe and easily
affect other parts of the same building.
2.10 There is an increase in the use of plastic products and in particular
uPVC for renovation work on the exterior of buildings and we consider
their use should be examined in more detail. As the work is frequently
for small repair and maintenance work, detailed planning permission
may not be required and the application is unlikely to be covered
by any fire regulations.
2.11 The uPVC window frames in the Irvine fire were stated to have
melted. This is a common occurrence with this type of thermoplastic
and has occurred in other fires. We have had experience of a plastic
soffit lining board melting and molten plastic falling on fire fighters
below. The molten material also helped to spread the fire within the
building although the product had been used for an exterior application.
In this case, the plastic soffit board was destroyed which then enabled
the fire to enter the roof space and spread throughout the building.
One fatality occurred. A picture showing this fire is included.
2.12 Our understanding is that at present the DETR have no plans to
reconsider the relevant regulations. We think this ill-advised. We
also believe it is necessary to consider that contribution made to
the fire by burning plastic building materials and in particular foam
plastic cores of external composite cladding panels.

|
| 3.
The extent of the use of external cladding systems |
3.1 External cladding systems are widely used both in new building
and in refurbishment work. We understand the type of plastic cladding
used on the property in Irvine is widely used throughout Scotland.
However, we believe the fire spread and re-entry to the building was
probably a consequence of the PVC window framing and sills. We do
not think this type of alteration is widespread but it should be looked
into.

|
| 4.
The adequacy of the regulations pertaining to their use |
4.1 We believe the present regulations in England and Wales were revised
in 1991 to ensure that cladding systems did not spread fire and present
a risk. As a result of the experience with a fire that spread within
the cavity behind an external cladding system, the Approved Document
B was changed to specify that combustible insulation was precluded
from external wall construction in buildings with a storey at over
20m above ground level. The Scottish regulations were amended in 1997,
after fears that a fire could spread up a cavity. Since then, every
opening has had to have a seal.
4.2 We believe that not only should the external face of the cladding
be Class 0, in accordance with the regulations, the Class O standard
should also apply to the inner face of the cladding sheet where there
is a cavity behind the external sheet.
4.3 We do not consider there is adequate regulation governing the
use of plastic products on the exterior of buildings. Responsibility
for implementation may be split between Building Control and the Fire
Authorities and it is not always clear which authority is responsible
for renovation work.
4.4 We also wish to make a distinction in the regulations between
integral Class 0 materials and modified products. This should reflect
the different fire performance between a non combustible composite
cladding and one consisting of a metalBface foam plastic.

|
| 5.
What action may be necessary to counter any risks posed in existing
building and to avoid any risks in new buildings or alterations to
existing buildings |
5.1 We do not consider there should be a wholesale review of all external
cladding systems, as we are sure that the majority will have met regulatory
requirements. A more detailed study is, however, needed to examine
the fire behaviour of thermoplastic products when used in exterior
applications. When plastic window frames could be affected by fire
as a result of the design of external cladding systems, some form
of fire protection may be necessary to protect the frame. Alternatively,
fire barriers should be used to prevent fire ingress into the building.
5.2 Thermoplastic products should not be used in areas where they
could melt or be destroyed by fire and thus add to the spread of fire.
It may therefore be necessary to replace some of these plastic products
with materials of limited combustibility.
5.3 There is also widespread concern amongst many fire fighters about
the safety of external cladding systems consisting of metal faced
foam plastics. These systems will generally have Class 0 fire performance,
but in real fires the foam plastic lining can ignite and burn. This
helps to spread the fire via the building fabric and there will be
an increase in the generation of smoke and toxic fumes. Collapse is
also possible. We believe this subject is still being reviewed by
the DETR and consider more stringent controls a priority.

|
| 6.
Other matters which may arise in the course of questioning |
6.1 We have highlighted some problems with burning plastics which
this fire has raised. There is at present nothing in Building Regulations
to require control of smoke, fumes or burning droplets from building
materials. This should be rectified as the increasing use of plastic
materials means there will be further instances of burning or molten
plastic helping to spread the fire or causing injuries to fire fighters
or building occupants. The DETR should act to rectify this, especially
as Home Office Statistics consistently demonstrate how more people
die in fires after being overcome by smoke than any other cause.
6.2 We consider the use of Class 0 materials should be more stringently
controlled for external wall cladding. Products which can only achieve
this rating by means of surface treatments, coatings, foil coverings
or impregnation treatments should not be allowed.

6.3 Apart from the specific recommendations for improvement we have
proposed in our Memoranda, there is an overall broad but important
point to make. The Irvine incident once again illustrates the unpredictable
and unexpected nature of fire.
6.4 This view was well expressed recently (FSDG Seminar on Fire Issues,
House of Commons, February 1999) by Frith Hoehnke, an architect who
carried out the extensive revision of Scottish fire safety building
regulations which came into force in 1997. Mr Hoehnke then said: "I
would never advise a client to cut anything to do with fire to the
bone because, when I look at the fire reports of actual fires, the
most incredible things have happened. ... So far as fires are concerned
it is really the unexpected that defeats us on many occasions. Indeed,
it is usually when not just one thing goes wrong but one, two or three
things go wrong at the same time that all our defences are breached
and disaster strikes".
6.5 We concur with this opinion. It raised the question of whether
regulatory decisions about fire safety in buildings should be left
as they currently are within the BRAC or (in the case of Scotland)
the BSAC remit. Clearly both these bodies call in expert opinions
but they do not always reflect a full range of available specialist
experience.
6.6 The
Government is currently moving, through the Home Office, to establish
a Fire Safety Advisory Board which should bring this wider experience
to bear on all fire safety matters. Logically BRAC and BSAC should
work more closely with such a body. It might, indeed, finally emerge
as a Fire Safety Commission reviewing fire hazards in a continuous
and therefore more sensible way. These are, as we said, wider issues
but every single incident has its lessons to teach and the Irvine
fire should be another providing support for such a broader move.

|
FIRE
SAFETY DEVELOPMENT GROUP
6 July 1999
The Fire Safety Development Group is an alliance of eight leading
companies manufacturing structural fire safety products within the
UK and Europe.
|
|